Duke University Study Quantifies Benefits of Data Center Flexibility

Demand flexibility among data centers could reduce the need for new gas-fired generation needed to supply their energy consumption while driving development of additional renewables and cutting electricity prices, according to a report by Duke University’s Nicholas Institute for Energy, Environment and Sustainability.

The institute in 2025 released a major paper showing that small amounts of data center flexibility could unlock 100 GW of grid capacity to serve more of the large loads. (See US Grid Has Flexible ‘Headroom’ for Data Center Demand Growth.)

The new paper — “Data Centers and Generation Capacity over the Next Decade: Potential Benefits of Flexibility” — seeks to expand on that theme by looking at how data center flexibility could change the power system, co-author Martin Ross, a senior research economist, said.

“What I normally do is the longer-term capacity planning modeling around policy analysis,” Ross said in an interview. “And I was curious, in that longer-term context, how would flexibility sort of alter the capacity mix going forward.”

Investments in new combined cycle gas-fired plants are cut by 10-50% in the flexibility scenarios modeled, with the lower end of the range assuming data center demand flexibility that avoids consumption during just 1% of peak hours, the report finds.

The report studies both temporal and spatial flexibility (shifting compute load to other data centers in other regions) to offer the simultaneous ability to further reduce the need for new gas plants.

The flexibility scenarios include ones in which data centers curtail their entire load for 1 and 2% of net peak hours, and other scenarios assuming they can curtail by 20 or 50% during those hours. Other scenarios are combinations, modeling 20 and 50% demand flexibility with the ability, but not the requirement, to completely avoid the system peaks of 1 or 2% of net peak hours. A final scenario uses spatial flexibility to shift 50% of the data center demand in a state to other regions.

Ross focused on combined cycle rather combustion turbine plants because the formers’ higher capacity factors are better suited for steady data center loads.

“Normally you would think if you were reducing stress on the grid, you would first be reducing the need for peaking units,” he said. “But given sort of the overall demand growth that’s being expected in the system, that leads you a bit more towards the combined cycle units and makes the gas peakers a bit less useful, since it’s not efficient to run them all the time as a base load for the data centers.”

data center

Another graph from the report showing the difference in capacity additions based on flexibility scenarios | Duke University

Projected savings in capital investment, operational spending and fuel costs over the next decade range from $40 billion to $150 billion. Data center flexibility could see average electricity prices drop by $2.50 to $8/MWh, with retail customers seeing their bills be 0.5 to 2.8% lower.

The report generally found that greater demand response translated into need for fewer gas plants, with the variable demand matching up better with renewable output.

“Combining the 20% hourly flexibility case with the ability to shift up to 50% of each region’s initial data center demands into other regions allows the national grid to avoid up to two-thirds of the new [combined cycle natural gas] units that would have been built by 2035 as data centers move to regions with both less stress on the grid and higher renewable resources,” the report said.

While flexibility offers clear benefits to the grid, it is unclear how much data centers can offer, Ross said. Customer-facing demand for cloud services is generally inflexible, though the compute load for training AI can be shifted around.

“When I think of flexibility, I normally think of flexibility driven by cost savings as the motivation for the flexibility, and I’m not sure that is a major factor in the thinking right at the moment, versus a race to beat all the other models,” Ross said.

Still, if data centers are motivated to offer flexibility for other benefits such as speed-to-market, their flexibility would benefit all customers.

“I was surprised that the flexibility was having fairly significant effects on what data centers might end up paying because you’re avoiding those high-cost hours, and that sort of not only benefits the data centers, but benefits consumers more broadly,” Ross said.

CTC Global Partners with Google to Launch GridVista System

Advanced conductor manufacturer CTC Global is working with Google Cloud and Tapestry to launch the GridVista System, which combines conductors with fiberoptic cables to offer operators visibility along the entire transmission line.

GridVista’s line awareness, paired with Google Cloud and Tapestry’s artificial intelligence-powered tools, turn line data into actionable intelligence that can optimize grid capacity, prevent outages, cut wildfire risk and lower operational costs, the companies say.

CTC’s advanced conductor technology can double the capacity of an existing transmission line, having worked on 1,400 projects with more than 300 utilities in 65 countries, CEO J.D. Sitton said in an interview.

“Now with the GridVista System, we’re adding data-grade fiber optics to the product that enables the measurement of strain and temperature and capacity and events along the entire length of the power line; not at discrete points, but literally the entire length between substations,” Sitton said. “And so, GridVista really is providing an entirely new level of detail and insight into the operating status of the transmission lines.”

Unlike traditional dynamic line rating products that add sensors at discrete points along a transmission line, the fiber optics in GridVista give utilities full knowledge of what is happening.

“It’s a much higher degree of resolution and a much faster feedback loop to the utilities about an event: a line down, a hot spot, a lightning strike, a rifle shot, a tree branch falling on the power line. These sorts of things,” Sitton said. “We know about it immediately. We know exactly where it is.”

Combining that visibility with advanced conductors puts utilities in a position to operate more cheaply, he said.

“We save them money on the capacity upgrade, and we’re saving them money from an operations perspective, because they’re much smarter about how they dispatch their operating resources and their lines,” Sitton said. “We enable them to operate with a higher degree of reliability because they no longer have these blind spots in their operation between the substations where they’re guessing what’s going on or not going on with their power line.”

The growing demand from data centers that want to connect to the grid much faster than the industry has historically been able to add new power plants or transmission is leading to more demand for products like GridVista.

“I think probably for the first time, we’re seeing utilities in the United States and Western Europe realize that they are, in fact, capital constrained, and so they need to get more out of their existing systems faster than historically they’ve had to,” Sitton said. “So, all of these things are, I would say, accelerated by the dramatic pickup of demand from the data centers that’s creating an environment where the utilities are very open to much more capital and operating cost-efficient solutions.”

Utility customers increasingly have higher expectations for a safe and reliable grid, which can benefit from the awareness the new product unlocks, he added.

CTC had a pre-existing relationship with Google around speed-to-power for its data centers. With GridVista, Google Cloud helped with the user-interface system, and Tapestry is working on reforming grid operations.

“Google is using GridVista as the source for what they call ‘ground-truth data,’ so the fundamental operating data that will feed the capabilities of their software platforms,” Sitton said. “So, it’s basically a two-way street, and it’s really quite exciting to see the early reactions of some of the utilities that we’ve been engaging with about the combined capabilities.”

AI applications are starting to transform how the grid is operated as the industry adopts the technology.

“We’re starting to see utilities rethink how they dispatch their grids, how they respond to operating challenges within their operating assets, and how they think about the kind of the planning aspects of their system,” Sitton said. “So, the next round of interconnections, and the next retirements of generators along their transmission lines and … the way they plan for these things is fundamentally changing.”

Utilities move at different speeds, but the “thought leaders” in the industry are starting to roll out AI applications that improve their operations and planning, he added.

“Utilities are utilities,” Sitton said. “They are, by definition, some of the most conservative organizations on the planet, I think, for good reason. But they’re not all cut from the kind of the absolute conservative cloth, and so we are seeing many utilities moving much more quickly.”

State Briefs

IOWA

Lawmakers Seek to Standardize Renewable Facilities Regulations

A House subcommittee advanced a bill that would create standard language for counties to adopt pertaining to setbacks, moratoriums, property tax and other siting considerations for renewable facilities.

The bill would allow local authorities to determine things like setback standards, shadow flicker standards and sound limitations, but only within certain ranges set by the bill. The bill would still allow counties to place a single, temporary moratorium for up to six months on new wind projects, and it would not allow eminent domain to be used to acquire rights of way for construction or operation.

The bill heads to the House Commerce Committee.

More: Iowa Capital Dispatch

MAINE

House Backs Aggressive Emissions Cuts

The House voted 75-64 in favor of updating the state’s carbon allowance program, taking a more aggressive approach to cutting emissions from power plants.

Under current law, Maine is to lower its carbon emissions cap by 2.5% each year. The bill approved by the House would speed up that timeline and, starting later this decade, would sharply increase annual reductions. From 2027 to 2028, the allowable emissions would drop by 12.5%. The bill estimates the total carbon emissions allowance would decline by 90% over the next 10 years.

The bill now moves to the Senate.

More: News Center Maine

MARYLAND

Discounted Rates for Low-income Residents to Take Effect by 2027

The Public Service Commission issued an order that will allow low-income residents to receive a discounted electricity and gas rate.

The program, which will go into effect by Jan. 1, 2027, will automatically apply to most low-income customers who are signed up to receive assistance through the Office of Home Energy Programs. The program will have a tiered structure, so households with the lowest incomes would receive the most assistance. The goal, according to the PSC, is to bring households’ energy costs to 6% of their annual income. It’s not clear how the utilities will recover the costs for the program, but it would likely be spread among remaining ratepayers.

More: Maryland Matters

MISSOURI

PSC Approves Ameren Gas, Battery Plant Site

The Public Service Commission formally approved an agreement to allow Ameren to build a new natural gas plant and battery storage facility on the site of the retired Rush Island coal plant.

The Big Hollow Energy Center calls for an 800-MW natural gas plant alongside a 400-MW battery storage system.

Construction is slated to begin within the next year with operations set for 2028.

More: KTVI

NEW MEXICO

Senate Rejects Bill to Codify State’s Emissions Goals

The Senate voted 23-19 to kill a bill that would have codified emissions reduction goals into law.

Senate President Pro Tempore Mimi Stewart (D-Albuquerque) again attempted to codify the goals into state law based on a 2019 executive order by Gov. Michelle Lujan Grisham. Opponents said the bill would impact the food and fuel costs and hurt the state’s economy.

More: Source NM

OREGON

DOE Awards $12M to 24 Renewable Projects

The state Department of Energy selected 24 recipients to receive nearly $12 million in Community Renewable Energy Grant Program funds. The program supports planning and construction of renewable energy or energy resilience projects for Tribes, public bodies and consumer-owned utilities.

The DOE received 76 applications requesting over $46 million in the fourth round of grant funding. Awards were chosen on a competitive basis.

The program was created by the Legislature in 2021.

More: Solar Power World

TEXAS

Hood County Rejects Data Center Moratorium

Following more than eight hours of discussion, Hood County Commissioners voted 3-2 to reject a temporary moratorium on new industrial development, including data centers.

The failed moratorium would have paused new data center development for six months while the county studied impacts to water supplies, energy demand, air quality, wildlife and residents’ quality of life. It could have affected four projects in early planning.

Adding to the debate was a letter from state Sen. Paul Bettencourt (R-Houston), chair of the Senate Committee on Local Government, to Attorney General Ken Paxton, which warned counties had no constitutional or statutory authority to impose development moratoriums.

More: Texas Tribune

VIRGINIA

Bill Would Put More Costs on Data Centers, Slash Residential Rates

Sen. L. Louise Lucas (D-Portsmouth) introduced an amendment to a bill that would levy more energy costs on Dominion Energy data centers and save residential customers about $5.50/month. 

The amended bill would allow the State Corporation Commission to determine if it is in the public’s interest for large load customers to cover the cost of distributing power to data centers and for Dominion’s capacity auctions. If the SCC approves, those costs could shift to new and existing data centers through 2033. The SCC estimated average residential customers will see rates reduced by 3.4%, about $5.52 monthly, and the data center customers’ rate will increase by 15.8%.

The bill advanced out of the Senate Labor and Commerce Committee and heads to the Senate Finance Committee.

More: Virginia Mercury

WASHINGTON

Lawmakers Quickly Pass Bill to Penalize Coal Use

The House of Representatives voted 63-33 to pass a bill that would levy a new coal tax on TransAlta Corporation if it continues to operate its Centralia coal plant.

The bill is in response to a DOE emergency order issued to TransAlta in December, ordering the company to keep the plant available for operation for 90 days with possible extensions after that. The measure would remove tax and regulatory exemptions agreed to 15 years ago as part of the coal phaseout deal between TransAlta and the state. TransAlta idled the power plant in December to comply with a 2011 agreement to phase out coal power in the state by the end of 2025.

The bill heads to the Senate.

More: Washington State Standard

WISCONSIN

Democratic Lawmakers Propose Data Center Moratorium

A group of Democratic state lawmakers announced a proposal to enact a moratorium on data center construction.

The bill wouldn’t allow the construction of any data centers in the state until it establishes a data center planning authority and prohibits energy and water costs from being shifted to residential utility customers, among other things.

Several pieces of legislation to regulate data center construction have already been proposed in the Legislature. In January, Assembly Republicans passed a bill that would establish some regulations, but Democrats said it didn’t do enough to prevent costs from being passed on to regular consumers. 

More: Wisconsin Examiner

WYOMING

Nuclear Waste Referendum Fails House Vote

A measure to ban spent nuclear fuel waste storage failed to receive the two-thirds vote required to advance in the Legislature’s session.

The measure, which died on the House floor with a 32-30 vote, would have put a referendum on the next general election ballot to amend the state constitution to ban nuclear waste storage unless approved by voters on a case-by-case basis.

More: WyoFile

Company Briefs

Rivian Beats Q4 Expectations

Rivian Automotive beat Wall Street’s fourth-quarter expectations but cautioned it will continue losing money as it launches a next-generation vehicle.

The company was able to achieve its first annual gross profit of $144 million in 2025, including $120 million during the fourth quarter. Rivian’s full 2025 revenue, including $1.7 billion in Q4, was up 8% compared with $4.97 billion in 2024.

Rivian’s net loss in 2025 was $3.6 billion, an improvement from a loss of $4.75 billion in 2024.

More: CNBC

Anthropic to Cover Price Hikes Caused by Data Centers

Anthropic, the AI firm behind Claude, said it will cover any increases in electricity rates that result from its data centers.

The company pledged to pay for infrastructure upgrades required to connect its data centers and said it would try to bring new generation online to match data center needs.

Anthropic joins Microsoft and OpenAI in making similar commitments.

More: The Hill

Enbridge to Proceed with Renewables Projects in Wyoming, Texas

Enbridge approved two renewable projects in Wyoming and Texas, the company said during its fourth-quarter earnings call.

The projects are the $1.2 billion, 365-MW Cowboy Phase 1 project in Wyoming and the $400 million, 152-MW Easter onshore wind facility in Texas. Both are expected to be operational by the end of 2027.

More: Renewables Now

Federal Briefs

DOE Announces $175M to Modernize Coal Plants

DOE announced $175 million in funding for projects to modernize, retrofit and extend the life of coal-fired power plants.

The projects will update plants belonging to Appalachian Power, Buckeye Power, Duke Energy Carolinas, Kentucky Utilities, Monongahela Power and Ohio Valley Electric Corp.

More: DOE

New Mexico Demands DOE Fix for Federal Nuclear Waste Management

The New Mexico Environment Department (NMED) released a series of regulatory enforcement actions and demanded the U.S. Department of Energy expedite the cleanup of legacy nuclear and hazardous waste at the Los Alamos National Laboratory.

The state will also fine the department up to $16 million for violating groundwater safety standards. The regulators’ concerns date back decades, when Los Alamos buried nuclear and hazardous waste in unlined landfills, septic tanks and firing sites. DOE estimates roughly 500,000 cubic meters of legacy waste remains.

“The continued presence of a large volume of unremedied hazardous and radioactive waste demonstrates a longstanding lack of urgency by the U.S. Department of Energy and elevates the risk of waste storage failures,” the NMED wrote.

More: High Country News

Federal Lab Lays off More Workers

The National Laboratory of the Rockies, formerly known as the National Renewable Energy Lab, laid off 134 workers, according to lab spokesperson David Glickson.

The layoffs affected both research and operations workers. The lab had another layoff in May 2025 that affected 114 workers.

“These actions were taken to adjust to existing and projected funding levels and alignment with DOE priorities,” Glickson said.

More: Colorado Politics

PJM, Monitor Float Reserve Market Changes

PJM and the Independent Market Monitor are drafting proposals to rework the RTO’s reserve market.

Reserve performance has been a focus since PJM implemented a market overhaul in 2022, which was followed by a drop in performance. That was counterbalanced with a 30% adder to the reserve requirement in May 2023, a change PJM’s Emily Barrett said has allowed the RTO to maintain adequate reserves at increased costs to load. The adder was scaled back recently to 20% as average performance increased above 85%.

The RTO’s proposal would increase the penalties for synchronized reserves that fail to respond, replace primary reserves with a handful of more targeted products based on duration and how quickly the resource can respond, and shift procurement to nodal rather than sub-zonal. Barrett presented the package to the Reserve Certainty Senior Task Force (RCSTF) on Feb. 11.

The RCSTF’s work was one of several areas the PJM Board of Managers wrote is integral to the efforts to address rising data center load.

Barrett said the current penalty rate is based on the credits reserves received between events, which can result in widely varying penalty rates for resources in the same event. The logic driving the RTO’s proposal instead would use the amount paid to reserves between events. The rate would be set at the greater of:

    • the mean synchronized reserve clearing price over the past delivery year, broken into intervals set at the average number of days between deployments exceeding 10 minutes (there was an average of 18 days between 10-minute synchronized reserve events in 2025, with an average clearing price of $1,910/MWh); or
    • the maximum system marginal price in the 30 minutes after a resource underperformed.

Stakeholders said there has not been enough focus on why performance has been low, which should be addressed alongside discussions on how underperforming resources should be penalized. Untying the penalty rate from what a resource is paid, and setting it so high, could result in resources that receive a low or zero clearing price facing penalties in the thousands, they said. Resources also could be held responsible for PJM inaccurately modeling parameters.

Joel Romero Luna, a market analyst with the Independent Market Monitor, said it has been doing outreach since mid-2024 and found a lot of issues related to communications and personnel. Performance has improved since generation owners ironed those issues out, leaving inaccurate parameters as a primary driver of the low response rate. In particular, the ramp rate and economic maximum parameters tend to be based on averages rather than how a resource expects to respond.

Monitor Joe Bowring told RTO Insider resource performance had not dropped, but rather the response rate was low because of communications issues.

“There was no actual drop in performance, and PJM’s arbitrary increase in reserves was not justified and continues to be unsupported. The measured performance of some reserves was low because PJM was using antiquated communications technology. The technology issue has been significantly, but not completely, addressed,” he said.

Luna noted that the Monitor has recommended that PJM count overperformance when calculating the fleet response rate. When capturing both sides of reserve performance, he said the response rate is closer to 100%.

PJM’s Kevin Hatch added that while the outreach to the owners of underperforming resources has been led by the Monitor, RTO staff have been involved as well.

New Reserve Products

The RTO’s proposal would add a ramp/uncertainty reserves (RUR) product capable of responding in 10 minutes, which would come with its own reserve requirement, and an energy gap requirement met by a combination of reserves.

Barrett said primary reserves backfill needs not met by other products, but resources lack clear performance obligations and penalties for not meeting commitments.

The energy gap requirement would be tailored toward meeting operational needs identified on medium- and high-risk winter days, and the 30-minute secondary reserve requirement would serve as a backfill to ensure the largest system contingency is met.

The 30-minute RUR and 30-minute secondary reserve products both come with a four-hour minimum availability. Barrett said event duration is expected to become more important as battery storage becomes more common.

Vitol’s Jason Barker said the transparency of the new market design will be crucial to avoiding “black box pricing” with unexplainable variations in pricing.

IMM Proposal

The Monitor proposed to retain most of the reserve market structure, while changing the procurement requirements for 30-minute synchronized and primary reserves. Bowring said PJM should eliminate the adder on the grounds that it is not required for reliability and there is no demonstrated need for it.

The 30-minute reserve requirement would be defined as double the single largest contingency plus real-time uncertainty, defined as the two-hour forecast for wind, solar and load minus the forecasts used in real-time security-constrained economic dispatch 10 minutes in advance. The synchronized reserve requirement would be the single largest contingency plus the extended reserve requirement of 190 MW. The primary reserve requirement would be the larger of 150% of the largest contingency or real-time uncertainty.

Performance evaluation and penalties would remain the same for synchronized reserves. For non-synchronized reserves, they would be pegged to the evaluation and penalty rules for secondary reserves. Reserve resources would be required to be capable of operating for four hours or longer.

Bowring told RTO Insider the proposal would capture the uncertainty of wind and solar generation in the reserve requirement based on analysis of actual resource behavior. PJM has not shown there is a need for larger market design changes, he argued, and its proposal appears designed to increase energy market revenues while failing to fully reflect energy and ancillary market revenues in the capacity market.

“We do not believe that PJM has supported its proposals with analysis, and we do not agree that it’s appropriate to use the demand curve for reserves to increase energy market revenues,” he said. “PJM has not demonstrated the existence of an ‘energy gap’ despite multiple different approaches, and PJM has not demonstrated the need for making the reserve markets more complicated.”

Devendra Canchi, a senior analyst with the Monitor, said PJM’s proposal would go too far and increase costs with no corresponding benefit. He presented part of the Monitor’s proposal during the RCSTF’s meeting Jan. 28.

Some stakeholders argued that the Monitor’s position is not backed with analysis and PJM could save costs by modeling reserves in SCED and accounting for them in transmission constraints.

Bowring responded that the proposal is fully supported and that any nodal distribution scheme would be arbitrary.

“No one knows where the next generation trip or forecast error will occur. PJM’s proposal would increase market costs by arbitrarily redispatching expensive resources with no defined benefit,” Bowring told RTO Insider.

Deputy Monitor Catherine Tyler said adding constraints would increase ratepayer costs, and any assumptions PJM makes about when supply is going to be lost run the risk of being inaccurate. While it’s important to ensure that reserves are deliverable, PJM’s proposal would not accomplish that, she argued.

NERC Staff Outline Growing LTRA Challenges

SAVANNAH, Ga. — NERC Director of Reliability Assessment and System Analysis John Moura acknowledged recent criticism of NERC’s Long-Term Reliability Assessment but emphasized the report is “not a prediction of outages [or] a forecast of impending blackouts.”

Speaking at the ERO’s quarterly technical session Feb. 12, he also discussed some of the ways the ERO’s approach to the assessment is changing in light of ongoing changes to the electric grid.

Moura’s remarks came the same week as his appearance, along with NERC CEO Jim Robb, at the Feb. 9 board meeting of the Organization of MISO States to discuss objections by OMS members to the ERO’s 2025 LTRA, which rated five assessment regions, including MISO, as having the potential to develop into high risk between 2026 and 2030.

The assessment means that planned resources as of July 2025 would lead to energy shortfalls in excess of resource adequacy targets or baseline criteria for unserved energy or loss of load.

OMS members disputed this label in a letter that argued NERC should have counted resources in MISO’s fast-track interconnection queue. The organization argued that the 11 GW of natural gas generation and battery storage proposals to come online by mid-2028 should make up for the 7-GW shortfall projected in the LTRA. (See MISO States Dispute ‘High Risk’ Designation from NERC.)

It was the second time in as many years that MISO objected to NERC’s assessment of the region’s risk. In 2025 MISO’s Independent Market Monitor pointed out that NERC had committed an error in rating the region as high-risk in the previous year’s LTRA. After a back-and-forth, NERC agreed to downgrade MISO to “elevated” risk.

At the technical session, Moura explained — as he did at the OMS board meeting — that NERC’s deadline for including energy projects passed in mid-July 2025 and MISO’s fast-track projects “were only approved in September, [so] were unable to be included in the energy analysis.” (See NERC to OMS: Long-term Assessment not a Predictor of Risk.) He added that the resources might not have been included in the assessment anyway because of changes to how NERC assesses the impact of generation additions.

“Counting capacity is really a thing of the past. Energy adequacy cannot be determined by counting capacity,” Moura said. “These projects weren’t left out because we missed them. The issue is really modelability, deliverability and certainty.”

Moura explained that modelability refers to whether any constraints could apply to a resource — for example, if a gas generator is coming online without firm gas arrangements — that could make it “difficult or impossible for that new generator to get gas on peak winter days.”

Deliverability means the ability of electricity generated in one area to reach load centers in other areas, which Moura observed could be an issue for the 7 GW of fast-track resources “south of the well-known MISO South to MISO North interconnection constraint.”

Finally, Moura defined certainty as the assurance that projected resources will be available as expected, an important question “given the supply chain challenges … in our assessments showing delays of up to 50% of planned generation not meeting their in-service dates.”

Avoiding Panic

Along with the difficulty assessing new generation, NERC Trustee Ken DeFontes observed that in previous LTRAs, NERC staff have also had problems predicting generation retirements because they “tended to only count retirements that had been announced [when] the reality was … it was likely more were coming.” He asked how the team behind the 2025 assessment had accounted for the issue.

Mark Olson, NERC’s manager of reliability assessments, replied that the ERO aims to account for both the “certain level of retirements in terms of being announced and in the process to be deactivated, versus a more speculative industry projection of potential retirement.” Moura added that NERC also must consider retirements as “a dial that can be turned … where states and other policy makers can take action to keep units online [or] have the ability to throttle those resources.”

Karen Onaran, CEO of the Electricity Consumers Resource Council, reminded attendees of the growing influence of NERC’s reliability assessments on lawmakers and policy makers, and warned that without proper context the reports could be “used as ammunition [to] saddle consumers with costs that may not be necessary.”

“At least within the last couple of years, when these reports come out, [they raise] some panic, and [hurt] some feelings. And we take it, and we try to take the lessons learned and figure it out,” Onaran said. She suggested that NERC’s Engagement and Outreach Committee, launched in December 2025 to handle external communications, work on a plan for conveying “what this report really says … and what risks it’s identifying … to all levels of government and to the industry.”

Navigating Extreme Winter Storms: A System-of-systems Perspective

In late January, the mass of cold air — typically held at bay by the high-level upper atmosphere winds that occur 10-30 miles above the North Pole — staged a jailbreak. A breakdown of the polar vortex occurs every so often when sudden stratospheric warming occurs (that’s what occurred during 2021’s devastating Winter Storm Uri), disrupting the vortex and allowing fugitive cold air to spill southwards, bringing extremely cold temperatures in its path. Collision with low-pressure systems can create a volatile cocktail of ice and snow.

That’s exactly what happened when the much-anticipated Winter Storm Fern swept across the country at the end of January. The southeastern U.S. suffered the brunt of physical damage, as high-level warmth brought rain that froze as it encountered cold air close to the ground, coating power lines with ice, breaking equipment and leaving approximately 1 million people without power.

Peter Kelly-Detwiler

Most damage came from ice on distribution networks, with Entergy estimating 860 poles and 60 substations out of service. Some larger transmission lines also were affected. Entergy reported 30 transmission lines out, and the Tennessee Valley Authority also saw as many as two dozen high-voltage transmission lines affected.

While thousands of customers went without power for many days, and the damage to the distribution system was serious, the bulk power system in the southeastern U.S. generally held its ground. The same was true for other regions of the country that got mostly snow but saw extreme cold prevail from Texas to New England.

This stands in stark contrast with winter storms Uri (February 2021 — with its extended system-wide outages in Texas) and Elliott (December 2022 — with outages in TVA and Duke service territories, while PJM barely squeaked by).

Thermal Plants, the Winter Workhorse

While prices spiked across multiple markets, the grid remained intact. There were several major reasons for that, with the underlying factors varying by region, but thermal plant reliability was a key theme. Gas generation was a critical player, but coal and oil also filled the gaps to meet surging demand. A review of several grids illustrates the point.

    • ISO-NE: New England saw dual-fuel plants switch over from gas to oil, burning through about half of the region’s stored oil reserves in late January and early February, with oil-fired generation surpassing gas for a couple of days. The grid operator requested a Department of Energy waiver to avoid emissions penalties.
    • PJM: The Mid-Atlantic grid operator commented that during the “strongest sustained cold period that the PJM system has experienced since the 1990s” it saw an average 18 to 19 GW of outages (compared with an expected 15.9 GW), with plant equipment failure as the greatest cause. Tight gas supplies also were a concern. In response, PJM called upon 5.2 GW of oil-fired capacity “that would otherwise have been restricted,” aided by a DOE order waiving emissions restrictions.
    • MISO: MISO ran coal generation more heavily than normal, including three of the five coal plants whose retirement was delayed by the Trump administration, delivering a total of 965 MW during much of the period from Jan. 21 to Feb. 1.
    • ERCOT: ERCOT also made it through, with its improved weatherization and inspection programs of power plants and transmission facilities reducing generation outages. Increased reserves, more flexible operations (including increased dual-fuel capabilities) and a growing deployment of batteries also helped.

We learned, once again, that our nation’s power grids rely on a significant fossil mix when the weather turns nasty. Coal-fired generation soared across the lower 48 states during the week ending Jan. 25, up 31% from the prior week and representing 21% of power generation, while gas stood at 38% and nuclear at 18%.

| EIA

We also learned that events on the grid are increasingly ripe for being politicized. Less than two weeks after the storm had passed, DOE issued a fact sheet declaring that “Beautiful, clean coal was the MVP of the huge cold snap we’re in right now,” and decrying the actions of the previous administration’s “energy subtraction policies which threatened America’s grid reliability and affordability.”

It seems that such politics are sadly unavoidable these days. But let’s try and remove politics from the conversation and focus on the facts. It’s not controversial to state that during the coldest days that occur every so often, fossil thermal generation — whether oil, coal or gas — is extremely valuable in keeping the lights on. Renewables and storage can pitch in, but they are a long way away from being able to handle that task.

As an example, when this article was drafted (Feb. 13), renewables made up 10% of the generation mix in ISO-NE at 3:30 p.m. In addition, on this clear and sunny day, rooftop solar cut peak demand by about 5,000 MW, with the duck curve exerting its influence on net demand. So, a combination of utility-scale and on-site renewables can generate energy and cut the use of fossil fuels.

However, that solar doesn’t address the evening peak, and it doesn’t help after heavy snow. The day after Fern departed New England, nearly all the panels in the region were blanketed with snow and the duck was hibernating, with no visible impact to be seen. As a dependable resource that can provide both capacity and needed energy, neither variable wind nor solar check the box.

Batteries can help meet peaks and address this issue of renewable energy droughts, if those storage assets can be fed by renewables, and renewable energy shortfalls are of relatively limited duration. That equation may change if we eventually get the long-duration, 100-hour batteries promised by start-up companies such as Noon and Form Energy, and those storage resources are deployed in enormous quantities at affordable prices. But we’re not there yet.

Addressing the Demand-side Thermal Issue

At the same time, much of the peak demand that occurs during extreme cold or hot spells could be greatly mitigated if we started to more accurately frame those peaks as a thermal problem, stemming from the need to heat or cool our built spaces. The better we insulate those spaces, the less volatility we would see in resulting energy demand.

EPA reports that homes can save an average of 15% on heating and cooling costs by employing a variety of insulation technologies. This need not be a herculean task, and insulation is effective. For example, upgrading U.S. homes to a 2009 building code could keep residences above 40 degrees Fahrenheit for nearly two days in sub-zero temperatures.

Maintaining a reliable and cost-effective grid is not, and never has been, a strictly supply-side issue. Rather, the power grid’s various supply and transmission technologies, combined with demand-side technologies, comprise a massive system of systems that can best be made economical, reliable and resilient if it is viewed and addressed as such. But such an approach requires sophisticated thinking that defies the simplistic and easy answers that many politicians and some analysts proffer.

Climate is an Even More Complex System of Systems

Perhaps counterintuitively, the polar vortex breaks down when it experiences spikes in the stratospheric temperatures, known as sudden stratospheric warmings. When those breakdowns occur, some areas of warmer air pour into the Arctic while lobes of polar air flee southwards. Nobody fully understands the dynamics behind this, but models suggest that climate change may be a driving force. If so, then we can add that to the lengthy list of other climate-related issues that justify cutting carbon emissions from our energy systems.

| NOAA

To pretend that we can oversimplify either the power grid or the impacts of human activity on the earth’s climate is a mistake. Each of these complex systems — and their interactions with each other — deserves far more scrutiny and understanding than most of us are willing to devote. We need more data and information, not less, and to entertain more nuanced conversations as well.

Around the Corner columnist Peter Kelly-Detwiler of NorthBridge Energy Partners is an industry expert in the complex interaction between power markets and evolving technologies on both sides of the meter.

N.Y. Cancels Solicitation but Remains Committed to OSW

After 19 months, New York has abandoned its most recent attempt to procure offshore wind power, saying it would not be prudent to proceed amid federal policy uncertainty.

The decision is only the latest setback for a state that, despite multiple cancellations and cost escalations, has the largest offshore wind pipeline in the nation.

New York presented it as a delay, not an end, of its offshore wind ambitions.

In the same week that it canceled the procurement, New York issued a request for information on ways to keep the industry from further atrophy; told an industry conference that offshore wind remains an important part of its energy strategy; and approved the structure of the offshore wind renewable energy credit (OREC) system that subsidizes increasingly expensive construction.

New York launched its fifth offshore wind solicitation July 17, 2024. It attracted 25 proposals totaling 6,870 MW from four bidders — Attentive Energy, Community Offshore Wind, Ørsted and Vineyard Offshore.

Attentive withdrew its proposals in October 2024, and Ørsted in August 2025.

Attentive Partner TotalEnergies and Community partner RWE said in November 2024 and April 2025 respectively that they would put their wind energy development efforts in U.S. waters on hiatus because of the political uncertainty surrounding offshore wind.

And of course, Donald Trump was re-elected president in November 2025 with a promise to block offshore wind development and has been trying to follow through for 13 months.

Given all this, the New York State Energy Research and Development Authority (NYSERDA) announced Feb. 13 that it was canceling the fifth solicitation.

A spokesperson said: “Federal actions disrupted the market and instilled significant uncertainty into offshore wind project development. Given the current level of uncertainty, it would not be prudent to enter into new long-term OREC purchase and sale agreements at this time, and as such, NYSERDA has concluded ORECRFP24-1 without award.”

With that, four out of five of New York’s solicitations are now dead ends.

The two contracts awarded in the 2018 solicitation (to Empire Wind 1 and Sunrise Wind) were canceled because cost escalations rendered the contracts unprofitable. The two contracts totaling 2.6 GW awarded in the 2020 solicitation were canceled for the same reason. And the three projects totaling 4 GW chosen in the 2022 solicitation were rendered untenable when General Electric halted development of the specified turbine.

Only the 2023 solicitation — a rush effort to salvage the state’s imploding offshore wind portfolio — has yielded steel in the water: Empire Wind 1 and Sunrise Wind (1.73 GW combined) are now under construction, at much greater cost than first agreed on.

But that is more than other states with offshore wind aspirations can say.

With the 132-MW South Fork Wind (which was completed in 2024 outside the NYSERDA procurement structure), New York now has three wind farms spinning or being built off its coast.

No other state has more than one, and most have none.

Speaking to Oceantic Network’s IPF 2026 on Feb. 10 in New York City, NYSERDA President Doreen Harris reiterated the state’s commitment to offshore wind despite Trump’s persistent efforts to destroy the sector, including one stop-work order against Sunrise and two against Empire. (See U.S. Offshore Wind Supporters Map Path Forward.)

It is an important part of New York’s strategy to meet rising power demand, she said: “To be clear, offshore wind remains a central part of how we get from here to there on the order of 7 GW of incremental capacity between now and 2040.”

That is a telling detail.

New York’s official offshore wind goal, established by its landmark 2019 climate law and specified on NYSERDA’s own website, has been 9 GW by 2035.

‘Meaningful Step’

So New York is pushing the timeline back and potentially changing the path but not abandoning the effort.

NYSERDA on Feb. 10 issued a request for information (RFI) seeking industry input on a potential predevelopment support program by which the state would enable the private sector to “continue investing responsibly in their lease areas to advance project development during a period of federal uncertainty, so that projects are well positioned to move forward efficiently when federal conditions become more favorable.”

One potential approach for this could be co-investment by the state, Harris said.

Also looking forward, NYSERDA on Oct. 2, 2025, proposed an offshore wind implementation plan that among other things structures the OREC system to reduce impacts on electric utility ratepayers, including through sales to voluntary third parties.

The Public Service Commission approved the plan at its Feb. 12 meeting (case 15-E-0302). PSC Chair Rory Christian said in a news release: “The commission acted to ensure the orderly management of the OSW program and corresponding sale of OSW Renewable Energy Certificates (ORECs) by NYSERDA when the program becomes operational. Our decision today will benefit residential and commercial customers by ensuring that ratepayer costs related to offshore wind development are reduced.”

The New York Offshore Wind Alliance issued a statement supportive of the state’s three policy moves.

“We understand NYSERDA’s decision to close the 2024 offshore wind solicitation without awards was because the original proposals were based on a completely different federal landscape,” said Alicia Gene Artessa, director of the industry group.

“We are strongly supportive of NYSERDA’s recent RFI exploring a predevelopment model for offshore wind solicitation. We believe that fundamentally changing how New York procures offshore wind energy is the right path forward while we adapt to the current federal instability.”

And she said: “We are also encouraged to see that the PSC approved NYSERDA’s Offshore Wind Implementation Plan yesterday. This is a meaningful step from the PSC to allow for more flexibility in the sale of ORECs and ensure our current under-construction projects continue to be managed effectively.”

N.J. Targets Data Centers in New Source Push

New Jersey legislators have advanced a bill that would protect ratepayers from rate hikes triggered by data center development as the state looks for ways to add generation capacity, boost its infrastructure and curb energy use.

A Senate and an Assembly committee each backed S731. It would require the New Jersey Board of Public Utilities to develop a tariff to set special rates for “large load data centers” with a maximum monthly demand of at least 100 MW.

Also moving ahead were unrelated bills to require data centers to report their water and electricity use, to boost solar development and to study how advanced transmission technologies can help the state. The BPU also announced rates would be flat in the next period, which starts June 1.

The tariff set up by the BPU under S731 would shelter ratepayers from rate increases stemming from “increased electricity demand caused by large load data centers.” The tariff also should “incentivize large load data centers to develop and utilize methods to increase energy efficiency, including through the use of technologies that capture and utilize the heat produced by the large load data center.”

To submit a commentary on this topic, email forum@rtoinsider.com.

To make sure investments in the state yield their full potential benefits over time, the legislation requires the state’s four utilities to ensure data centers provide financial guarantees they will “take at least 85% of service they request for a period of not less than 10 years.” Data centers must show the proposed project is “unique and not duplicative of any other large load data center project” in or out of state.

The Senate Economic Growth Committee backed the bill 3-1. The Assembly Telecommunications and Utilities Committee backed a version 9-0 after testimony that showed vigorous support for the legislation.

Data Center Reporting Requirements

Preparing for the predicted dramatic increase in data centers and ensuring they pay for themselves without overly burdening ratepayers is central to the state’s efforts.

Analysts say one cause for the predicted energy shortfall is that the state, like others in PJM, has closed aging, fossil-fueled resources more rapidly than new, mainly clean energy sources have come online.

In a separate vote that also focused on data centers, the Senate Environment and Energy Committee backed S3379, which would require data center owners or operators to compile a water and energy use report to the BPU every six months. The BPU would publish the information, according to the bill, which passed without comment.

The data center tariff, while drawing mainly supportive testimony, demonstrated the complexity of the issue. Some legislators expressed concern that the state should avoid creating obstacles that could deter data centers from coming to the state, but most speakers focused on ratepayer benefits.

“Ultimately, this is about cost fairness for the people of New Jersey,” said Assemblyman David Bailey Jr. (D), a bill sponsor and committee member. “This is about us looking out for our constituents and their best interests and the overall health of New Jersey electrical grid.”

Zach Landesini, a resident of Vineland, N.J., said he sees the need for the legislation in the experience of his community with the development of a 700,000-square-foot data center by Data One, whose website says it will use 350 MW. Landesini said he envisions scenarios that emerge, and which the bill could address.

He said the project will draw 15% of its power from the local grid, and added: “What would happen if Data One needed to draw a larger portion of their power from the local grid?”

“How would this affect local ratepayers?” he asked. “This could happen for a variety of reasons, including technical deficiencies in power generation, and site expansion.”

Supply Side Pressure

Brian O. Lipman, director of the New Jersey Division of Rate Counsel, also backed the bill, but acknowledged that it couldn’t shield ratepayers from all the cost hikes associated with a data center. One committee member asked him how the state could calculate the increased cost of power when rates increased due to a data center pulling a large volume of power from the grid, effectively reducing the supply for everyone else.

“On the supply side, there’s not a lot we here can do, other than if we want to build generation somehow to add more supply,” he said. “What we can do is, and what we are doing is, we’re pressuring PJM: First of all, don’t sign up a data center if you don’t have the power to serve them.”

He noted that an alternative, outlined in a separate bill, would require new data centers to “bring their own generation.” But if New Jersey passed such a law and other states in PJM do not, data center developers would simply build outside of New Jersey, which nevertheless would bear that cost through its participation in the RTO, he said.

Harnessing New Technology

The debate over how the state addresses the looming energy shortfall, and the added pressure on generation and grid systems from data centers, stepped up in earnest in June 2025, when a 20% rate hike on the average electricity bill took effect.

Gov. Mikie Sherrill (D), who took office in January, pledged in her election campaign to freeze rates. Her first executive orders upon taking office laid out a range of measures designed to do so and boost state generating capacity, in part by accelerating solar development. (See New N.J. Governor Rapidly Confronts Electricity Crisis.)

In that vein, the Assembly Telecommunications and Utilities Committee moved ahead a bill, A3969, that would extend the state’s current goal of incentivizing 3,750 MW of solar power by 2026 to one of incentivizing 750 MW per year through 2035.

The Senate Economic Development committee backed a bill that seeks to prepare the state’s infrastructure for future stress by using advanced transmission technologies (ATT). S2189 would require the BPU to evaluate the “attributes, functions, costs and benefits of ATT” and look at whether it could “enable an electric public utility to provide safe, reliable and affordable electricity to its customers, considering existing and planned transmission infrastructure and projected demand growth.”

The bill defines ATT as any software or hardware technology that increases the capacity, efficiency, reliability or safety of an existing or new electric transmission facility, including grid-enhancing technology and advanced or high-performance conductors.

Rate Hikes Temporarily Avoided

BPU President Christine Guhl-Sadovy announced the results of the state Basic Generation Service auction conducted in early February. The results, which largely are shaped by the PJM capacity auction, will mean the average electricity bill stays roughly the same when the new rates take effect June 1.

The minimal increase or slight decline for some ratepayers depending on their utility is due largely to a “collar” PJM agreed to place on its prices, limiting their increase, because of lawsuits filed by New Jersey and other states. Sherrill has advocated for an extension of the collar, Guhl-Sadovy said.

“I think we would anticipate there to be a higher price if we don’t have a collar,” she said. “Because we have significant load growth and so we need to get more generation and more capacity through things like demand response in order to meet that kind of load growth.”

She acknowledged the collar is a temporary measure and the trajectory of future rates is primarily in the hands of PJM. And she noted that Sherrill outlined a series of initiatives to hold down rates and increase generation capacity in her first two executive orders. They included boosting solar and battery storage power and creating a virtual power plant strategy.

“Those things will not have an overnight impact on capacity prices, but they will certainly put downward pressure on capacity prices, because we will have more generation bidding into the capacity market,” she said.